MULTICLUSTER 12 FOR SUNNY ISLAND

Easy creation of powerful on- and off-grid applications
SMA-Multicluster.jpg

Proven technology with new application areas for PV systems – the SMA Multicluster System 12 is now suitable for operation on the utility grid as well. In Germany, it complies with the applicable conditions for connection to the low-voltage grid of VDE-ARN 4105: With the battery inverters Sunny Island 6.0H or 8.0H and the NA-Box 12, commercial self-consumption and batterybackup systems of up to 100 kWp can be set up. On an international scale, the Grid-Connect-Box 12 can be used to form self-consumption and battery-backup systems with an output of up to 138 kWp. The new Multicluster-Box 12 is suitable for TN- and TT-grids thanks to the integrated grounding contactor. In areas with very unstable utility grids, a diesel generator can also be connected. For off-grid regions, the Multicluster-Box 12 allows powerful solar off-grid systems with up to 138 kWp to be set up – ideal for commercial enterprises and village power supplies in rural regions.

Flexible

  • For off-grid, on-grid and back-up applications
  • For power range of 30 to 138 kW
  • For TN- and TT-grids


Easy to use

  • Integrated AC distribution for Sunny Island, generator, PV and loads (MC-Box 12)
  • Retrofittable grid connection (NA-Box 12, Grid-Connect-Box12)
  • Better serviceability


Safe and reliable

  • Fulfills German VDE-AR-N 4105
  • Integrated residual-current device
  • Active anti-islanding

 

  Multicluster-Box 12
Load connection
Number of connections 1 x three-phase
Rated power 138 kW
Rated grid voltage 230 V / 400 V
AC voltage range

172,5 V - 265 V

300 - 433 V

Current at rated values 3 x 200 A
Terminals for connection N, L1, L2, L3 Spring-cage terminals
Fuse / maximum permissible fuse sizes NH1 / 200 A
Sunny Island connections
Maximum number of devices 12
Ac rated power / AC current at rated values 72 kW / 12 x 26 A
Rated operating voltage 230 V / 400 V
Terminal for connection N, PE, L Spring-cage terminals
Fuse 12 x circuit braker C40 A
Generator Connection
Number of connections 1 x trhee-phase
Rated grid input power 138 kW
Nominal Voltage 230 V / 400 V
AC input current 3 x 200 A
Terminals for connection N, PE, L1, L2, L3 Spring-case terminals
Fuse / maximum permissible fuse sizes NH1 / 200 A
PV System connection
Number of connection 1 x three-phase
Rated power 138 kW
Rated operationg voltage 230 V / 400 V
AC current at rated values 3 x 200 A
Terminals for connection N, PE, L1, L2, L3 Spring-cage terminals
Maximum permissible back-up fuse 200 A
NA-Box / Grid-Connect-Box connection
Number of connections 1 x three-phase
Rated input power 138 kW
Rated operating voltage 230 V / 400 V
Rated current / AC input current 3 x 200 A
Terminals for connection N, PE, L1, L2, L3 Spring-cage terminals
Maximum permissible back-up fuse 200 A
General Data
Number of phases 3
Permited grid configuration TN-S, TN-C S y TT
Rated frequency / frequency range 50 Hz / 45 ... 65 Hz.
Dimensions ( W x H x D ) 1200 x 1600 x 435 mm
Weight 200 Kg
Maximum operating altitude above mean sea level 3000 m
Degree of protection according to IEC 60529 IP55
EMC environment, interference / interference immunity B / A
Humidity 0 ... 100 %
Operating temperature range -25 ºC ... +60 ºC
Output power / rated power at 25 ºC 138 kW
Output power / rated power between 25 and 60 ºC See "Derating Behavior" diagram
Data cables Yes
Warranty 5 years

 

Sunny Island, Li-Ion approved batteries

SMA Multicluster 12 for Sunny Island